NFPA-20 — stationary pumps for fire protection
NFPA-20 is the standard published by the US National Fire Protection Association covering the selection, installation, and acceptance testing of stationary fire pumps. Despite being a US document, it is widely adopted internationally — and in Brazil it is referenced directly by NBR 16704.
The current edition is NFPA 20: 2025.
What NFPA-20 specifies
| Topic | Section (2025 edition) | Summary |
|---|---|---|
| Pump types allowed | Ch. 6 | Horizontal split-case, end-suction, vertical in-line, vertical turbine |
| Performance curve | §6.2 | At 150% of rated flow, head must be ≥65% of rated head; at shut-off, head ≤140% of rated |
| Drivers | Ch. 9, 11 | Electric motor, diesel engine, or steam turbine |
| Controllers | Ch. 10, 12 | Listed/approved controllers, automatic + manual |
| Jockey pump | §4.27 | Maintains pressure to prevent main-pump short-cycling |
| Acceptance testing | §14.2 | Hydrostatic, flow test at 100/150% of rated, controller test |
The 65/100/140 curve rule
The single most-cited rule from NFPA-20:
Head, % of rated
│
140% ●───╮ shut-off (max)
│ ╲
100% │ ● rated point
│ ╲
65% │ ● 150% flow (min)
│
└─────────────────── Flow, % of rated
0 100 150
A fire pump curve must lie inside this envelope. A pump that exceeds 140% at shut-off can over-pressure the system at idle. A pump that drops below 65% at 150% flow cannot deliver demand under fire conditions.
What FB Bombas builds
The fire-pump systems line is built specifically to NFPA-20 + NBR 16704 and ships with the listed controllers, jockey pump, and complete documentation package required for fire-marshal acceptance.
See also our fire-pump factory page.
Further reading
References
- NFPA 20: 2025 — Standard for the Installation of Stationary Pumps for Fire Protection.
- UL 448 — Centrifugal Stationary Pumps for Fire-Protection Service.
- FM Class 1319 — Approval Standard for Centrifugal Fire Pumps.